Section 914 Page 201 Date April 2006
AURORA FIRE PUMPS VERTICAL TURBINE
Supersedes Section 914 Page 201 Dated May 2004
Use the following table to determine which discharge head should be used on vertical turbine fire pumps. Both style discharge heads are shown on the setting plans where applicable. Rated Capacity (GPM) 250 300 400 500 750 750 1000 1000 1250 1500 1500 2000 2000 2500 3000 3500 4000 4500
© 2011 Pentair Pump Group, Inc.
Bowl Design 10 FEM 10 FEM 10 FEM 11 FGM 12 FCM 14 FGM 12 FCM 14 FGM 13 FGH 13 FGH 15 FGH 15 FGH 17 FGM 15 FGH 19 FGM 19 FGM 19 FGH 19 FGH
Discharge Head Design 100-175 PSI Working Pressure U.L. Listed FM Approved 16-1/2 x 6 SDC 16-1/2 x 6 SDC 16-1/2 x 6 SDC 16-1/2 x 6 SDC 16-1/2 x 6 SDC 16-1/2 x 6 SDC 16-1/2 x 6 LAD 16-1/2 x 6 LAD 16-1/2 x 6 LAD 16-1/2 x 6 LAD 16-1/2 x 8 SDC 16-1/2 x 8 SDC 16-1/2 x 6 LAD 16-1/2 x 6 LAD 16-1/2 x 8 SDC 16-1/2 x 8 SDC 16-1/2 x 8 SDC 16-1/2 x 8 SDC 16-1/2 x 8 SDC 16-1/2 x 8 SDC 20 x 10 LAD 20 x 10 LAD 20 x 10 LAD 20 x 10 LAD 20 x 10 LAD 20 x 10 LAD 20 x 10 LAD 20 x 10 LAD 24-1/2 x 12 SDH 24-1/2 x 12 SDH 24-1/2 x 12 SDH 24-1/2 x 12 SDH 24-1/2 x 12 SDH 24-1/2 x 12 SDH 24-1/2 x 12 SDH 24-1/2 x 12 SDH
176-300 PSI Working Pressure U.L. Listed or FM Approved 16-1/2 x 6 LAD 16-1/2 x 6 LAD 16-1/2 x 6 LAD 16-1/2 x 6 LAD 16-1/2 x 6 LAD 16-1/2 x 8 LAD 16-1/2 x 6 LAD 16-1/2 x 8 LAD 16-1/2 x 8 LAD 16-1/2 x 8 LAD 20 x 10 LAD 20 x 10 LAD 20 x 10 LAD 20 x 10 LAD 24-1/2 x 12 SDH 24-1/2 x 12 SDH 24-1/2 x 12 SDH 24-1/2 x 12 SDH
Section 914 Page Date April 2006
202
AURORA FIRE PUMPS ELECTRIC DRIVEN VERTICAL TURBINE
Supersedes Section 914 Page 202 Dated May 2004
S T
S
U DIA CL DISCH
T
B N
(4) H DIA HOLES BASEPLATE TOP VIEW
CL DISCHARGE
A
C
3/4" NPT DRAIN G NPT
F
(O.A.L.)
NOTES 1. Flange ratings are either 125# or 250# and will be designated in the certification block below for each order submittal. 2. Not for construction, installation, or application purposes unless certified. Dimensions shown are typical and may vary due to various tolerances. 3. All bases are designed to have full contact with either grout or a soleplate grouted in place. 4. Limited to maximum working pressure of 175 PSI. 5. For 250 GPM Z = 21”. For 300 GPM and 400 GPM Z = 24”.
NOMINAL COLUMN DIA
V
Z MIN WATER LEVEL
W Y
12 MIN
BOTTOM OF PIT
Size & Model
# of Stages
10 FEM
4
11 FGM
4 3
12 FCM
BOWL ASSEMBLY, COLUMN & SHAFTING Nominal Column Dia. V UL & FM Water All Others UL & FM Water All Others W Y Lube Only Lube Only 6 6 41 41 6 10 Total Stages Add 8.25 for each additional stage over 4 stages 6 8 44-13/16 47-9/16 9 11-1/2 Total Stages Add 9-1/2 for each additional stage over 4 stages 8 8 40 42-3/4 7 13 Total Stages Add 10-3/4 for each additional stage over 3 stages
Z (5) 34 34
DISCHARGE HEADS & BASEPLATES Size BD 12 16-1/2 16-1/2 16-1/2
DISCH 6 SDH 6 SDC 6 LAD 6 SDH
A 20 23 23 20
B 11-1/2 11-3/8 10-1/4 11-1/2
C 7 10 10 7
Customer:
F 1 1-1/2 1-1/2 1
G 3/4 1 1 3/4
H 1 7/8 7/8 1
S 21-1/2 24 24 21-1/2
T 17-5/32 21 21 17-5/32
P.O.#: UL
Model:
# Stages:
Motor Mfg.:
HP:
GPM: Frame:
U 14-1/2 17-1/8 17-1/8 14-1/2
(4)
Dwg.#
Job Name:
Certified By:
N 1-3/8 1-1/16 1-1/16 1-3/8
FM
CUL
Flange Rating:
PSI: Ph:
Hz:
125#
250#
Max. Lift: V:
Encl.:
Date:
© 2011 Pentair Pump Group, Inc.
Section 914 Page Date May 1, 2004
AURORA FIRE PUMPS ELECTRIC DRIVEN VERTICAL TURBINE
203
Supersedes Section 914 Page 203 Dated June 1, 2002 S T
S
U DIA CL DISCH
T
B N
(4) H DIA HOLES BASEPLATE TOP VIEW
CL DISCHARGE
A
C
3/4" NPT DRAIN G NPT
F
(O.A.L.)
NOMINAL COLUMN DIA
NOTES 1. Flange ratings are either 125# or 250# and will be designated in the certification block below for each order submittal. 2. Not for construction, installation, or application purposes unless certified. Dimensions shown are typical and may vary due to various tolerances. 3. All bases are designed to have full contact with either grout or a soleplate grouted in place. 4. Limited to maximum working pressure of 175 PSI.
V
Z MIN WATER LEVEL
W 12 MIN
Y
BOTTOM OF PIT
Size & Model
# of Stages
13 FGH
4
14 FGM
3
15 FGH
3
BOWL ASSEMBLY, COLUMN & SHAFTING Nominal Column Dia. V UL & FM Water All Others UL & FM Water All Others W Y Lube Only Lube Only 8 10 61-13/16 65-1/4 11 13 Total Stages Add 13-1/16 for each additional stage over 4 stages 8 10 44-15/16 49-1/4 13 14-3/4 Total Stages Add 12-3/16 for each additional stage over 3 stages 10 12 54-1/16 57-7/16 13 14-3/4 Total Stages
Z 34 30 34 - 2000 GPM 46 - 2500 GPM
Add 14-1/2 for each additional stage over 3 stages DISCHARGE HEADS & BASEPLATES
Size BD 16-1/2 16-1/2 20
DISCH 8 SDH 8 LAD 10 LAD
A 23 23 23
B 11-3/8 11-3/8 13-7/8
C 10 10 10-1/2
F 1-1/2 1-1/2 1-1/2
Customer:
G 1 1 1
H 7/8 7/8 7/8
N 1-3/16 1-3/16 1-1/4
U 17-1/8 17-1/8 17-1/8
# Stages:
Motor Mfg.:
HP:
GPM: Frame:
FM
CUL
Flange Rating:
PSI: Ph:
Date:
(4)
Dwg.# UL
Model:
© 2011 Pentair Pump Group, Inc.
T 21 21 21
P.O.#:
Job Name:
Certified By:
S 24 24 24
Hz:
Max. Lift: V:
Encl.:
125#
250#
Section 914 Page 204 Date May 1, 2004
AURORA FIRE PUMPS ELECTRIC DRIVEN VERTICAL TURBINE
Supersedes Section 914 Page 204 Dated June 1, 2002
S T
S
U DIA CL DISCH
T
B N
(4) H DIA HOLES
CL DISCHARGE
A
BASEPLATE TOP VIEW
C
3/4" NPT DRAIN G NPT
F
(O.A.L.)
NOMINAL COLUMN DIA
NOTES 1. Flange ratings are either 125# or 250# and will be designated in the certification block below for each order submittal. 2. Not for construction, installation, or application purposes unless certified. Dimensions shown are typical and may vary due to various tolerances. 3. All bases are designed to have full contact with either grout or a soleplate grouted in place.
V
Z MIN WATER LEVEL
W 12 MIN
Y
BOTTOM OF PIT
Size & Model
# of Stages
17 FGM
3
19 FGM
2
19 FGH
2
BOWL ASSEMBLY, COLUMN & SHAFTING Nominal Column Dia. V UL & FM Water All Others UL & FM Water All Others W Y Lube Only Lube Only 12 N/A 49-7/8 N/A 9 18 Total Stages Add 13-1/2 for each additional stage over 3 stages 12 N/A 47-5/8 N/A 12 23-1/2 Total Stages Add 17-5/8 for each additional stage over 2 stages 12 N/A 47-5/8 N/A 12 23-1/2 Total Stages Add 17-5/8 for each additional stage over 2 stages
Z 28 32 32
DISCHARGE HEADS & BASEPLATES Size BD 20 24-1/2
DISCH 10 LAD 12 SDH
A 23 28
B 13-7/8 17
C 10-1/2 13-1/2
F 1-1/2 2
Customer:
G 1 3/4
H 7/8 1-1/8
N 1-1/4 1-7/8
T 21 26-5/32
U 19 24-1/2
P.O.#:
Dwg.#
Job Name:
UL
Model:
# Stages:
Motor Mfg.:
HP:
Certified By:
S 24 32-1/2
GPM: Frame:
FM
CUL
Flange Rating:
PSI: Ph:
Hz:
125#
250#
Max. Lift: V:
Encl.:
Date:
© 2011 Pentair Pump Group, Inc.
Section 914 Page 205 Date September 2011
AURORA FIRE PUMPS DIESEL DRIVEN VERTICAL TURBINE
Supersedes Section 914 Page 205 Dated May 2004 CD
S T
T S
CS
FACE OF DRIVE DISK
U DIA CL DISCH
COUPLING GUARD
MAXIMUM VERTICAL OFFSET IS .25”
HP (4) H DIA HOLES
B N
HD
BASEPLATE TOP VIEW
1/2
AA
Mfg.
GEAR Ratio
DISCHARGE
A CE
4 AN DIA HOLES
AB
C
AB AF
Model
F
G NPT COOLING SUPPLY FOR ENG
CL OF ENGINE
(O.A.L.)
3/4" NPT DRAIN
CC CA
NOMINAL COLUMN DIA
NOTES 1. Flange ratings are either 125# or 250# and will be designated in the certification block below for each order submittal. Reducers and/or increasers may be required to meet NFPA Pamphlet #20. 2. Not for construction, installation, or application purposes unless certified. Dimensions shown are typical and may vary due to various tolerances. 3. All bases are designed to have full contact with either grout or a soleplate grouted in place. 4. Limited to maximum working pressure of 175 PSI 5. CD, CE & CS are dimensioned to face of drive disk. 6. For 250 GPM Z = 21”. For 300 GPM and 400 GPM Z = 24”.
V
Z MIN WATER LEVEL
W 12 MIN
Y
BOTTOM OF PIT
Size & Model
# of Stages
10 FEM
4
11 FGM
4
BOWL ASSEMBLY, COLUMN & SHAFTING Nominal Column Dia. V UL & FM Water All Others UL & FM Water All Others W Y Lube Only Lube Only 6 6 41 41 6 10 Total Stages Add 8-1/4 for each additional stage over 4 stages 6 8 44-13/16 47-9/16 9 11-1/2 Total Stages Add 9-1/2 for each additional stage over 4 stages
Z (6) 34
DISCHARGE HEADS & BASEPLATES Size BD 16-1/2 16-1/2
DISCH 6 SDC 6 LAD
A 23 23
B 11-3/8 10-1/4
MODEL JU4HUF10 JU4HUF20 JU4HUF30 JU4HUF40
AA 32 32 32 32
AB 15 15 15 15
AF 5 5 5 5
C 10 10
H 7/8 7/8
N 1-1/16 1-1/16
S 24 24
T 21 21
CLARKE JU4H DIESEL ENGINES AN CA CB CC 1x2 40 N/A 30 1x2 40 N/A 30 1x2 40 N/A 30 1x2 40 N/A 30
CD 35.75 35.75 35.75 35.75
CE 2.26 2.26 2.26 2.26
CS 10 10 10.5 10.5
Customer:
F 1-1/2 1-1/2
G 1 1
P.O.#:
Job Name: # Stages:
Engine Mfg.:
Engine Model:
Certified By:
© 2011 Pentair Pump Group, Inc.
GPM:
FM
CUL
HP 40.5 40.5 45 45
Flange Rating:
PSI: RPM:
Date:
HD 20.25 20.25 20.25 20.25
(4)
Dwg.# UL
Model:
U 17-1/8 17-1/8
Max. Lift: HP:
125#
250#
Section 914 Page 206 Date September 2011
AURORA FIRE PUMPS DIESEL DRIVEN VERTICAL TURBINE
Supersedes Section 914 Page 206 Dated April 2006
CD
S T
T S
CS
FACE OF DRIVE DISK
U DIA CL DISCH
COUPLING GUARD
MAXIMUM VERTICAL OFFSET IS .25”
HP (4) H DIA HOLES
B N
HD
BASEPLATE TOP VIEW
AA
GEAR Ratio
Mfg.
CE
4 AN DIA HOLES
AB
C
AF
Size & Model
# of Stages
12 FCM
3
13 FGH
4
F
G NPT COOLING SUPPLY FOR ENG
CL OF ENGINE
AB
Model
NOTES 1. Flange ratings are either 125# or 250# and will be designated in the certification block below for each order submittal. Reducers and/or increasers may be required to meet NFPA Pamphlet #20. 2. Not for construction, installation, or application purposes unless certified. Dimensions shown are typical and may vary due to various tolerances.
DISCHARGE
A 1/2
(O.A.L.)
3/4" NPT DRAIN
CC CA
3. All bases are designed to have full contact with either grout or a soleplate grouted in place. 4. Limited to maximum working pressure of 175 PSI 5. CD, CE & CS are dimensioned to face of drive disk.
NOMINAL COLUMN DIA
V
Z MIN WATER LEVEL
BOWL ASSEMBLY, COLUMN & SHAFTING Nominal Column Dia. V UL & FM Water All Others UL & FM Water All Others W Y Z Lube Only Lube Only 8 8 40 42-3/4 7 13 34 Total Stages Add 10-3/4 for each additional stage over 3 stages 8 10 61-13/16 65-1/4 11 13 34 Total Stages Add 13-1/16 for each additional stage over 4 stages
W 12 MIN
Y
BOTTOM OF PIT
DISCHARGE HEADS & BASEPLATES Size BD 12 16-1/2 16-1/2 16-1/2 16-1/2
DISCH 6 SDH 8 SDC 8 LAD 6 LAD 6 SDH
A 23 23 23 23 21-1/2
B 11-1/2 11-3/8 11-3/8 10-1/4 11-1/2
MODEL JU4HUF10 JU4HUF20 JU4HUF30 JU4HUF40 JU4HUF50
AA 32 32 32 32 32
AB 15 15 15 15 15
AF 5 5 5 5 5
C 8-1/2 10 10 10 8-1/2
H 1 7/8 7/8 7/8 1
N 1-3/8 1-3/16 1-3/16 1-1/16 1-3/8
S 21-1/4 24 24 24 21-1/4
T 17-5/32 21 21 21 17-5/32
CLARKE JU4H DIESEL ENGINES AN CA CB CC 1x2 40 N/A 30 1x2 40 N/A 30 1x2 40 N/A 30 1x2 40 N/A 30 1x2 40 N/A 30
CD 35.75 35.75 35.75 35.75 35.75
CE 2.26 2.26 2.26 2.26 2.26
CS 10 10 10.5 10.5 15.2
Customer:
F 1-1/2 1-1/2 1-1/2 1-1/2 1-1/2
G 3/4 1 1 1 3/4
P.O.#:
Job Name: # Stages:
Engine Mfg.:
Engine Model:
Certified By:
HD 20.25 20.25 20.25 20.25 20.25
(4)
HP 40.5 40.5 45 45 45
Dwg.# UL
Model:
U 14-1/2 17-1/8 17-1/8 17-1/8 14-1/2
GPM:
FM
CUL
Flange Rating:
PSI: RPM:
125#
250#
Max. Lift: HP:
Date:
© 2011 Pentair Pump Group, Inc.
Section 914 Page 207 Date September 2011
AURORA FIRE PUMPS DIESEL DRIVEN VERTICAL TURBINE
Supersedes Section 914 Page 207 Dated May 2004
CD
S T
T S
CS
FACE OF DRIVE DISK
U DIA CL DISCH
COUPLING GUARD
MAXIMUM VERTICAL OFFSET IS .25”
HP (4) H DIA HOLES
B N
HD
BASEPLATE TOP VIEW
1/2
AA
CE
4 AN DIA HOLES
AB
C
AF
GEAR
CA
Model
NOMINAL COLUMN DIA
NOTES 1. Flange ratings are either 125# or 250# and will be designated in the certification block below for each order submittal. Reducers and/or increasers may be required to meet NFPA Pamphlet #20. 2. Not for construction, installation, or application purposes unless certified. Dimensions shown are typical and may vary due to various tolerances.
Size & Model
# of Stages
14 FGM
3
15 FGH
3
(O.A.L.)
3/4" NPT DRAIN
CC
Ratio
F
G NPT COOLING SUPPLY FOR ENG
CL OF ENGINE
AB
Mfg.
DISCHARGE
A
3. All bases are designed to have full contact with either grout or a soleplate grouted in place. 4. Limited to maximum working pressure of 175 PSI 5. CD, CE & CS are dimensioned to face of drive disk.
V
Z MIN WATER LEVEL
W
BOWL ASSEMBLY, COLUMN & SHAFTING Nominal Column Dia. V UL & FM Water All Others UL & FM Water All Others W Y Lube Only Lube Only 8 10 44-15/16 49-1/4 13 14-3/4 Total Stages Add 12-3/16 for each additional stage over 3 stages 10 12 54-1/16 57-7/16 13 14-3/4 Total Stages
12 MIN
Y
Z BOTTOM OF PIT
36 34 - 2000 GPM 46 - 2500 GPM
Add 14-1/2 for each additional stage over 3 stages DISCHARGE HEADS & BASEPLATES
Size BD 16-1/2 16-1/2 20
DISCH 8 SDC 8 LAD 10 LAD
A 23 23 23
B 11-3/8 11-3/8 13-7/8
MODEL JU4HUF40 JU4HUF50
AA 32 32
AB 15 15
AF 5 5
C 10 10 10-1/2
H 7/8 7/8 7/8
N 1-3/16 1-3/16 1-1/4
S 24 24 24
T 21 21 21
CLARKE JU4H DIESEL ENGINES AN CA CB CC 1x2 40 N/A 30 1x2 40 N/A 30
CD 35.75 35.75
CE 2.26 2.26
CS 10.5 15.2
Customer:
F 1-1/2 1-1/2 1-1/2
G 1 1 1
P.O.#:
Job Name: # Stages:
Engine Mfg.:
Engine Model:
Certified By:
© 2011 Pentair Pump Group, Inc.
GPM:
FM
CUL
HP 45 45
Flange Rating:
PSI: RPM:
Date:
HD 20.25 20.25
(4)
Dwg.# UL
Model:
U 17-1/8 17-1/8 17-1/8
Max. Lift: HP:
125#
250#
Section 914 Page 208 Date September 2011 Supersedes Section 914 Page 208 Dated April 2006
S
AURORA FIRE PUMPS DIESEL DRIVEN VERTICAL TURBINE CD
S T
T
CS
FACE OF DRIVE DISK
U DIA CL DISCH
COUPLING GUARD
MAXIMUM VERTICAL OFFSET IS .35”
HP (4) H DIA HOLES
B N
HD
BASEPLATE TOP VIEW
1/2
AA
GEAR Ratio
Mfg.
CE
4 AN DIA HOLES
AB
C
AB AF
NOTES 1. Flange ratings are either 125# or 250# and will be designated in the 3. All bases are designed to have full contact with either grout certification block below for each order submittal. Reducers and/or or a soleplate grouted in place. increasers may be required to meet NFPA Pamphlet #20. 4. CD,CD & CS are dimensioned to face of drive disk. 2. Not for construction, installation, or application purposes unless certified. Dimensions shown are typical and may vary due to various tolerances.
11 FGM
4
12 FCM
3
(O.A.L.)
3/4" NPT DRAIN
CC CA
# of Stages
F
G NPT COOLING SUPPLY FOR ENG
CL OF ENGINE
Model
Size & Model
DISCHARGE
A
NOMINAL COLUMN DIA
V
Z MIN WATER LEVEL
BOWL ASSEMBLY, COLUMN & SHAFTING Nominal Column Dia. V UL & FM Water All Others UL & FM Water All Others W Y Z Lube Only Lube Only 6 8 44-13/16 47-9/16 9 11-1/2 34 Total Stages Add 9-1/2 for each additional stage over 4 stages 8 8 40 42-3/4 7 13 34 Total Stages Add 10-3/4 for each additional stage over 3 stages
W 12 MIN
Y
BOTTOM OF PIT
DISCHARGE HEADS & BASEPLATES Size BD 12 16-1/2
DISCH 6 SDH 6 LAD
A 23 23
B 11-1/2 10-1/4
MODEL JU6HUF30 JU6HUF50 JU6HUF60
AA 32 32 32
AB 15 15 15
AF 5 5 5
C 8-1/2 10
F 1-1/2 1-1/2
G 3/4 1
H 1 7/8
CLARKE JU6H DIESEL ENGINES AN CA CB CC 1x2 46 N/A 36 1x2 46 N/A 36 1x2 46 N/A 36
Customer:
S 21-1/4 24
T 17-5/32 21
CD 45.9 45.9 48
CE .88 .88 .88
CS 15.2 15.2 15.2
P.O.#:
Job Name: # Stages:
Engine Mfg.:
Engine Model:
U 14-1/2 17-1/8
HD 20.35 20.35 20.35
HP 45.8 45.8 45.8
Dwg.# UL
Model:
Certified By:
N 1-3/8 1-1/16
GPM:
FM
CUL
Flange Rating:
PSI: RPM:
125#
250#
Max. Lift: HP:
Date:
© 2011 Pentair Pump Group, Inc.
Section 914 Page 209 Date September 2011
AURORA FIRE PUMPS DIESEL DRIVEN VERTICAL TURBINE
S
CS
FACE OF DRIVE DISK
U DIA CL DISCH
T
Supersedes Section 914 Page 209 Dated May 2004
CD
S T
COUPLING GUARD
MAXIMUM VERTICAL OFFSET IS .35”
HP (4) H DIA HOLES
B N
HD
BASEPLATE TOP VIEW
AA
CE
4 AN DIA HOLES
AB
C
Mfg.
AF
(O.A.L.)
3/4" NPT DRAIN
CC CA
Model
F
G NPT COOLING SUPPLY FOR ENG
CL OF ENGINE
AB
GEAR Ratio
DISCHARGE
A 1/2
NOMINAL COLUMN DIA
NOTES 1. Flange ratings are either 125# or 250# and will be designated in the 3. All bases are designed to have full contact with either grout certification block below for each order submittal. Reducers and/or or a soleplate grouted in place. increasers may be required to meet NFPA Pamphlet #20. 4. Limited to maximum working pressure of 175 PSI 2. Not for construction, installation, or application purposes unless certified. 5. CD, CE & CS are dimensioned to face of drive disk. Dimensions shown are typical and may vary due to various tolerances.
V
Z MIN WATER LEVEL
W 12 MIN
Y
Size & Model
# of Stages
13 FGH
4
15 FGH
3
BOWL ASSEMBLY, COLUMN & SHAFTING Nominal Column Dia. V UL & FM Water All Others UL & FM Water All Others W Y Lube Only Lube Only 8 10 61-13/16 65-1/4 11 13 Total Stages Add 13-1/16 for each additional stage over 4 stages 10 12 54-1/16 57-7/16 13 14-3/4 Total Stages
BOTTOM OF PIT
Z 34 34 - 2000 GPM 46 - 2500 GPM
Add 14-1/2 for each additional stage over 3 stages DISCHARGE HEADS & BASEPLATES
Size BD 16-1/2 16-1/2 20
DISCH 8 SDC 8 LAD 10 LAD
A 23 23 23
B 11-3/8 11-3/8 13-7/8
MODEL JU6HUF30 JU6HUF50 JU6HUF60
AA 32 32 32
AB 15 15 15
AF 5 5 5
C 10 10 10-1/2
F 1-1/2 1-1/2 1-1/2
G 1 1 1
H 7/8 7/8 7/8
CLARKE JU6H DIESEL ENGINES AN CA CB CC 1x2 46 N/A 36 1x2 46 N/A 36 1x2 46 N/A 36
Customer:
T 21 21 21
CD 45.9 45.9 48
CE .88 .88 .88
CS 15.2 15.2 15.2
# Stages:
Engine Mfg.:
Engine Model:
GPM:
HD 20.35 20.35 20.35
FM
CUL
(4)
HP 45.8 45.8 45.8
Flange Rating:
PSI: RPM:
Date:
U 17-1/8 17-1/8 17-1/8
Dwg.# UL
Model:
© 2011 Pentair Pump Group, Inc.
S 24 24 24
P.O.#:
Job Name:
Certified By:
N 1-3/16 1-3/16 1-1/4
Max. Lift: HP:
125#
250#
Section 914 Page 210 Date September 2011
AURORA FIRE PUMPS DIESEL DRIVEN VERTICAL TURBINE
Supersedes Section 914 Page 210 Dated May 2004
CD
S T
T S
CS
BARE FLYWHEEL
U DIA CL DISCH
COUPLING GUARD
MAXIMUM VERTICAL OFFSET IS .35”
HP (4) H DIA HOLES
B N
HD
BASEPLATE TOP VIEW
1/2
AA
CE
4 AN DIA HOLES
AB
C
Mfg.
AF
Model
F
G NPT COOLING SUPPLY FOR ENG
CL OF ENGINE
AB
GEAR Ratio
DISCHARGE
A
(O.A.L.)
3/4" NPT DRAIN
CC CA
NOMINAL NOTES COLUMN DIA 1. Flange ratings are either 125# or 250# and will be designated in the certification block below for each order submittal. 2. Not for construction, installation, or application purposes unless certified. Dimensions shown are typical and may vary due to various tolerances. 3. All bases are designed to have full contact with either grout or a soleplate grouted in place. 4. CD,CE & CS are dimensioned to bare flywheel.
V
Z MIN WATER LEVEL
Size & Model
# of Stages
11 FGM
4
12 FCM
3
BOWL ASSEMBLY, COLUMN & SHAFTING Nominal Column Dia. V UL & FM Water All Others UL & FM Water All Others W Y Z Lube Only Lube Only 6 8 44-13/16 47-9/16 9 11-1/2 34 Total Stages Add 9-1/2 for each additional stage over 4 stages 8 8 40 42-3/4 7 13 34 Total Stages Add 10-3/4 for each additional stage over 3 stages
W 12 MIN
Y
BOTTOM OF PIT
DISCHARGE HEADS & BASEPLATES Size BD 16-1/2
DISCH 6 LAD
A 23
B 10-1/4
MODEL JW6HUF30 JW6HUF50 JW6HUF60
AA 36 36 36
AB 17 17 17
AF 5 5 5
C 10
H 7/8
N 1-1/16
S 24
T 21
U 17-1/8
CLARKE JW6H DIESEL ENGINES AN CA CB CC 1x2 46 N/A 36 1x2 46 N/A 36 1x2 46 N/A 36
CD 47.52 47.52 47.52
CE 2.9 2.9 2.9
CS 14.1 14.1 14.1
HD 24 24 24
Customer:
F 1-1/2
G 1
P.O.#:
Job Name: # Stages:
Engine Mfg.:
Engine Model:
Certified By:
Dwg.# UL
Model:
HP 50.11 50.11 50.11
GPM:
FM
CUL
Flange Rating:
PSI: RPM:
125#
250#
Max. Lift: HP:
Date:
© 2011 Pentair Pump Group, Inc.
Section 914 Page 211 Date September 2011
AURORA FIRE PUMPS DIESEL DRIVEN VERTICAL TURBINE
Supersedes Section 914 Page 211 Dated May 2004
CD
S T
T S
CS
BARE FLYWHEEL
U DIA CL DISCH
COUPLING GUARD
MAXIMUM VERTICAL OFFSET IS .35”
HP (4) H DIA HOLES
B N
HD
BASEPLATE TOP VIEW
1/2
AA
CE
4 AN DIA HOLES
AB
C
Mfg.
AF
Model
F
G NPT COOLING SUPPLY FOR ENG
CL OF ENGINE
AB
GEAR Ratio
DISCHARGE
A
(O.A.L.)
3/4" NPT DRAIN
CC CA
NOMINAL COLUMN DIA
NOTES 1. Flange ratings are either 125# or 250# and will be designated in the certification block below for each order submittal. 2. Not for construction, installation, or application purposes unless certified. Dimensions shown are typical and may vary due to various tolerances. 3. All bases are designed to have full contact with either grout or a soleplate grouted in place. 4. Limited to maximum working pressure of 175 PSI 5. CD, CE & CS are dimensioned to bare flywheel.
V
Z MIN WATER LEVEL
W
Size & Model
# of Stages
13 FGH
4
14 FGM
3
BOWL ASSEMBLY, COLUMN & SHAFTING Nominal Column Dia. V UL & FM Water All Others UL & FM Water All Others W Y Lube Only Lube Only 8 10 61-13/16 65-1/4 11 13 Total Stages Add 13-1/16 for each additional stage over 4 stages 8 10 44-15/16 49-1/4 13 14-3/4 Total Stages Add 12-3/16 for each additional stage over 3 stages
12 MIN
Y
Z BOTTOM OF PIT
34 36
DISCHARGE HEADS & BASEPLATES Size BD 16-1/2 16-1/2 20
DISCH 8 SDC 8 LAD 10 LAD
A 23 23 23
B 11-3/8 11-3/8 13-7/8
MODEL JW6HUF30 JW6HUF40 JW6HUF50 JW6HUF60
AA 36 36 36 36
AB 17 17 17 17
AF 5 5 5 5
C 10 10 10-1/2
F 1-1/2 1-1/2 1-1/2
G 1 1 1
H 7/8 7/8 7/8
CLARKE JW6H DIESEL ENGINES AN CA CB CC 1x2 46 N/A 36 1x2 46 N/A 36 1x2 46 N/A 36 1x2 46 N/A 36
Customer:
T 21 21 21
U 17-1/8 17-1/8 17-1/8
CD 49.4 49.4 49.4 49.4
CE 4.6 4.6 4.6 4.6
CS 19.7 19.7 19.7 19.7
HD 24 24 24 24
# Stages:
Engine Mfg.:
Engine Model:
GPM:
FM
CUL
HP 50.1 50.1 50.1 50.1
Flange Rating:
PSI: RPM:
Date:
(4)
Dwg.# UL
Model:
© 2011 Pentair Pump Group, Inc.
S 24 24 24
P.O.#:
Job Name:
Certified By:
N 1-3/16 1-3/16 1-1/4
Max. Lift: HP:
125#
250#
Section 914 Page 212 Date September 2011
AURORA FIRE PUMPS DIESEL DRIVEN VERTICAL TURBINE
Supersedes Section 914 Page 212 Dated May 2004
CD
S T
T S
CS
BARE FLYWHEEL
U DIA CL DISCH
COUPLING GUARD
MAXIMUM VERTICAL OFFSET IS .35”
HP (4) H DIA HOLES
B N
HD
BASEPLATE TOP VIEW
1/2
GEAR Ratio
Mfg.
DISCHARGE
A
AA
CE
4 AN DIA HOLES
AB
C
AB
Model
AF
(O.A.L.)
3/4" NPT DRAIN
CC
NOTES 1. Flange ratings are either 125# or 250# and will be designated in the certification block below for each order submittal. 2. Not for construction, installation, or application purposes unless certified. Dimensions shown are typical and may vary due to various tolerances. 3. All bases are designed to have full contact with either grout or a soleplate grouted in place. 4. CD, CE & CS are dimensioned to bare flywheel.
F
G NPT COOLING SUPPLY FOR ENG
CL OF ENGINE
CA NOMINAL COLUMN DIA
V
Z MIN WATER LEVEL
W
Size & Model
# of Stages
15 FGH
3
19 FGM
2
BOWL ASSEMBLY, COLUMN & SHAFTING Nominal Column Dia. V UL & FM Water All Others UL & FM Water All Others Lube Only Lube Only 10 12 54-1/16 57-7/16 Total Stages 12 Total Stages
N/A
12 MIN
Y
W
Y
Z
13
14-3/4
34 - 2000 GPM 46 - 2500 GPM
BOTTOM OF PIT
Add 14-1/2 for each additional stage over 3 stages 47-5/8 N/A 12 23-1/2 32 Add 17-5/8 for each additional stage over 2 stages
DISCHARGE HEADS & BASEPLATES Size BD 20 24-1/2
DISCH 10 LAD 12 SDH
A 23 28
B 13-7/8 17
MODEL JW6HUF30 JW6HUF40 JW6HUF50 JW6HUF60
AA 36 36 36 36
AB 17 17 17 17
AF 5 5 5 5
C 10-1/2 13-1/2
F 1-1/2 2
G 1 3/4
H 7/8 1-1/8
CLARKE JW6H DIESEL ENGINES AN CA CB CC 1x2 46 N/A 36 1x2 46 N/A 36 1x2 46 N/A 36 1x2 46 N/A 36
Customer:
S 24 32-1/4
T 21 26-5/32
CD 49.4 49.4 49.4 49.4
CE 4.6 4.6 4.6 4.6
CS 19.7 19.7 19.7 19.7
P.O.#:
Job Name: # Stages:
Engine Mfg.:
Engine Model:
U 17-1/8 24-1/2
HD 24 24 24 24
HP 50.1 50.1 50.1 50.1
Dwg.# UL
Model:
Certified By:
N 1-1/4 1-7/8
GPM:
FM
CUL
Flange Rating:
PSI: RPM:
125#
250#
Max. Lift: HP:
Date:
© 2011 Pentair Pump Group, Inc.
Section 914 Page 213 Date April 2006 Supersedes Section 914 Page 213 Dated May 2004
THIS PAGE LEFT INTENTIONALLY BLANK
© 2011 Pentair Pump Group, Inc.
Section 914 Page Date April 2006
214
Supersedes Section 914 Page 214 Dated May 2004
THIS PAGE LEFT INTENTIONALLY BLANK
© 2011 Pentair Pump Group, Inc.
Section 914 Page 215 Date April 2006 Supersedes Section 914 Page 215 Dated May 1, 2004
THIS PAGE LEFT INTENTIONALLY BLANK
© 2011 Pentair Pump Group, Inc.
Section 914 Page 216 Date April 2006 Supersedes Section 914 Page 216 Dated May 1, 2004
THIS PAGE LEFT INTENTIONALLY BLANK
© 2011 Pentair Pump Group, Inc.
Section Page 217 000 Page Section 914 217 Xxxxx XXXX Date Date April 2006 Supersedes Page217 217 SupersedesSection Section 000 914 Page Dated XXXXXXXXXXXXXXXXXX Dated May 1, 2004
THIS PAGE LEFT INTENTIONALLY BLANK
© 2011 Pentair Pump Group, Inc.
Section 914 Page 218 Date April 2006 Supersedes Section 914 Page 218 Dated May 1, 2004
THIS PAGE LEFT INTENTIONALLY BLANK
© 2011 Pentair Pump Group, Inc.
Section 914 Page 219 Date April 2006 Supersedes Section 914 Page 219 Dated May 2004
THIS PAGE LEFT INTENTIONALLY BLANK
© 2011 Pentair Pump Group, Inc.
Section 914 Page Date April 2006
220
Supersedes Section 914 Page 220 Dated May 2004
THIS PAGE LEFT INTENTIONALLY BLANK
© 2011 Pentair Pump Group, Inc.
Section 914 Page 221 Date April 2006 Supersedes Section 914 Page 221 Dated May 2004
THIS PAGE LEFT INTENTIONALLY BLANK
© 2011 Pentair Pump Group, Inc.
Section 914 Page 222 Date February 2008
AURORA FIRE PUMPS DIESEL DRIVEN VERTICAL TURBINE
Supersedes Section 914 Page 222 Dated May 2004
CD
S T
S
FACE OF DRIVE FLANGE
U DIA CL DISCH
T
COUPLING GUARD
MAINTAIN MINIMUM ANGLE OF 1˚ - 1-1/2˚
HP (4) H DIA HOLES
B N
HD
BASEPLATE TOP VIEW
1/2 6 (TYP)
AA
CE
8 AN DIA HOLES
AB
C
Ratio
Model
AF
3
CB
CB
CC CA
# of Stages
12 FCM
3
13 FGH
4
(O.A.L.)
3/4" NPT DRAIN NOMINAL COLUMN DIA
NOTES 1. Flange ratings are either 125# or 250# and will be designated in the certification block below for each order submittal. 2. Not for construction, installation, or application purposes unless certified. Dimensions shown are typical and may vary due to various tolerances. 3. All bases are designed to have full contact with either grout or a soleplate grouted in place. 4. Limited to maximim working pressure of 175 PSI. 5. CD, CD & shafting length are dimensioned to face of drive flange.
Size & Model
F
G NPT COOLING SUPPLY FOR ENG
CL OF ENGINE
AB
GEAR Mfg.
DISCHARGE
A
V
Z MIN WATER LEVEL
BOWL ASSEMBLY, COLUMN & SHAFTING Nominal Column Dia. V UL & FM Water All Others UL & FM Water All Others W Y Z Lube Only Lube Only 8 8 40 42-3/4 7 13 34 Total Stages Add 10-3/4 for each additional stage over 3 stages 8 10 61-13/16 65-1/4 11 13 34 Total Stages Add 13-1/16 for each additional stage over 4 stages
W 12 MIN
Y
BOTTOM OF PIT
DISCHARGE HEADS & BASEPLATES Size BD 16-1/2 16-1/2 16-1/2
DISCH 6 LAD 8 SDC 8 LAD
A 23 23 23
B 10-1/4 11-3/8 11-3/8
MODEL 3406DIT
AA 28-1/2
AB 10-1/4
AF 10-3/4
C 10 10 10
F 1-1/2 1-1/2 1-1/2
G 1 1 1
CATERPILLAR DIESEL ENGINES AN CA CB 13/16 76 16-3/4
Customer:
H 7/8 7/8 7/8
N 1-1/16 1-3/16 1-3/16
S 24 24 24
T 21 21 21
CC 16-3/4
CD 78-5/8
CE 15-1/8
HD 19-1/2
Dwg.# UL
Model:
# Stages:
Motor Mfg.:
HP:
GPM: Frame:
(4)
HP 34-3/4
P.O.#:
Job Name:
Certified By:
U 17-1/8 17-1/8 17-1/8
FM
CUL
Flange Rating:
PSI: Ph:
Hz:
125#
250#
Max. Lift: V:
Encl.:
Date:
© 2011 Pentair Pump Group, Inc.
Section 914 Page 223 Date February 2008
AURORA FIRE PUMPS DIESEL DRIVEN VERTICAL TURBINE
Supersedes Section 914 Page 223 Dated May 2004 CD
S T
S
FACE OF DRIVE FLANGE
U DIA CL DISCH
T
COUPLING GUARD
MAINTAIN MINIMUM ANGLE OF 1˚ - 1-1/2˚
HP (4) H DIA HOLES
B N
HD
BASEPLATE TOP VIEW
1/2 6 (TYP)
GEAR Ratio
Mfg.
AA
CE
8 AN DIA HOLES
AB
C
CB
AF
3
CB
CC CA
14 FGM
3
15 FGH
3
17 FGM
3
NOMINAL COLUMN DIA
W 12 MIN
Y
Z 30
BOTTOM OF PIT
34 - 2000 GPM 46 - 2500 GPM
Add 14-1/2 for each additional stage over 3 stages 49-7/8 N/A 9 18 Add 13-1/2 for each additional stage over 3 stages
N/A
V
Z MIN WATER LEVEL
BOWL ASSEMBLY, COLUMN & SHAFTING Nominal Column Dia. V UL & FM Water All Others UL & FM Water All Others W Y Lube Only Lube Only 8 10 44-15/16 49-1/4 13 14-3/4 Total Stages Add 12-3/16 for each additional stage over 3 stages 10 12 54-1/16 57-7/16 13 14-3/4 Total Stages 12 Total Stages
(O.A.L.)
3/4" NPT DRAIN
NOTES 1. Flange ratings are either 125# or 250# and will be designated in the certification block below for each order submittal. 2. Not for construction, installation, or application purposes unless certified. Dimensions shown are typical and may vary due to various tolerances. 3. All bases are designed to have full contact with either grout or a soleplate grouted in place. 4. Limited to maximum working pressure of 175 PSI. 5. CD, CE & shafting length are dimensioned to face of drive flange. 6. When used with a 17FGM, U=19 (483).
# of Stages
F
G NPT COOLING SUPPLY FOR ENG
CL OF ENGINE
AB
Model
Size & Model
DISCHARGE
A
28
DISCHARGE HEADS & BASEPLATES Size BD 16-1/2 16-1/2 20
DISCH 8 SDC 8 LAD 10 LAD
A 23 23 23
B 11-3/8 11-3/8 13-7/8
C 10 10 10-1/2
F 1-1/2 1-1/2 1-1/2
MODEL 3406DIT 3406DITA
AA 28-1/2 28-1/2
AB 10-1/4 10-1/4
AF 10-3/4 10-3/4
CATERPILLAR DIESEL ENGINES AN CA CB 13/16 76 16-3/4 13/16 76 16-3/4
Customer:
G 1 1 1
H 7/8 7/8 7/8
N 1-3/16 1-3/16 1-1/4
S 24 24 24
T 21 21 21
CC 16-3/4 16-3/4
CD 78-5/8 78-5/8
CE 15-1/8 15-1/8
HD 19-1/2 19-1/2
# Stages:
Motor Mfg.:
HP:
© 2011 Pentair Pump Group, Inc.
GPM: Frame:
FM
CUL
Flange Rating:
PSI: Ph:
Date:
(6)
Dwg.# UL
Model:
(4)
HP 32-3/4 35-1/8
P.O.#:
Job Name:
Certified By:
U 17-1/8 17-1/8 17-1/8
Hz:
Max. Lift: V:
Encl.:
125#
250#
Section 914 Page 224 Date February 2008 Supersedes Section 914 Page 224 Dated May 2004
S
AURORA FIRE PUMPS DIESEL DRIVEN VERTICAL TURBINE CD
S T
FACE OF DRIVE FLANGE
U DIA CL DISCH
T
COUPLING GUARD
MAINTAIN MINIMUM ANGLE OF 1˚ - 1-1/2˚
HP (4) H DIA HOLES
B N
HD
BASEPLATE TOP VIEW
1/2 6 (TYP)
AA
GEAR Ratio
Mfg.
CE
8 AN DIA HOLES
AB
C
AB
Model CB
AF
CB
CC CA
19 FGM
2
19 FGH
2
(O.A.L.)
3/4" NPT DRAIN
NOTES 1. Flange ratings are either 125# or 250# and will be designated in the certification block below for each order submittal. 2. Not for construction, installation, or application purposes unless certified. Dimensions shown are typical and may vary due to various tolerances. 3. All bases are designed to have full contact with either grout or a soleplate grouted in place. 4. CD, CD & shafting length are dimensioned to face of drive flange.
# of Stages
F
G NPT COOLING SUPPLY FOR ENG
CL OF ENGINE
3
Size & Model
DISCHARGE
A
NOMINAL COLUMN DIA
V
Z MIN WATER LEVEL
BOWL ASSEMBLY, COLUMN & SHAFTING Nominal Column Dia. V UL & FM Water All Others UL & FM Water All Others W Y Z Lube Only Lube Only 12 N/A 47-5/8 N/A 12 23-1/2 32 Total Stages Add 17-5/8 for each additional stage over 2 stages 12 N/A 47-5/8 N/A 12 23-1/2 32 Total Stages Add 17-5/8 for each additional stage over 2 stages
W 12 MIN
Y
BOTTOM OF PIT
DISCHARGE HEADS & BASEPLATES Size BD 24-1/2
DISCH 12 SDH
A 28
B 17
C 13-1/2
MODEL 3406DITA 3408DITA 3412DIT 3412DITA
AA 28-1/2 RTF RTF RTF
AB 10-1/4 RTF RTF RTF
AF 10-3/4 RTF RTF RTF
F 2
G 3/4
CATERPILLAR DIESEL ENGINES AN CA CB 13/16 76 16-3/4 RTF RTF RTF RTF RTF RTF RTF RTF RTF
Customer:
H 1-1/8
N 1-7/8
S 32-1/2
T 26-5/32
CC 16-3/4 RTF RTF RTF
CD 78-5/8 RTF RTF RTF
CE 15-1/8 RTF RTF RTF
HD 19-1/2 RTF RTF RTF
HP 35-1/8 RTF RTF RTF
P.O.#:
Dwg.#
Job Name:
UL
Model:
# Stages:
Motor Mfg.:
HP:
Certified By:
U 24-1/2
GPM: Frame:
FM
CUL
Flange Rating:
PSI: Ph:
Hz:
125#
250#
Max. Lift: V:
Encl.:
Date: